 • LT Power Capacitor
 • HT Power Capacitor
 • Special Type of Capacitor
 • Capacitor For Harmonic Filter Applications
 • Harmonic Filters
 • APFC Panels
 • AMC For Panel & Capacitor
 • System Harmonic Analysis & Solution

Nelf Healing Capacitors (IS 13585 : 1994) Technical Data
 
APP
www.kotakco.com
Capacitors are manufactured using Double Hazy Double thick Polypropylene film between two electrodes of thick Al foil (soft annealed 99.3% purity) & have extended foil construction to ensure low watt losses. The capacitors are impregnated with NPCB, Biodegradable impregnated & hermetically sealed. Current carrying capacity of APP capacitor is 250 times greater than MPP capacitor.
MXD
www.kotakco.com
Capacitors are manufactured using one layer of Tissue Paper & one layer of Polypropylene film between two electrodes of plain Al foil (soft, annealed,99.3% & above purity) Having extended foil design to ensure low watt losses. Tissue paper soaks the impregnate by capillary action ensuring perfect impregnation. PP film offers excellent insulation strength making capacitor stronger
 
APP (SL)
Type APP01 to APP025
Rated Voltage  (UN)  * 415V / 440V / 480V
Frequency 50 HZ
Max. Permissible Overvoltage 1.15 x UN
Max. Permissible Over current 1.7 x IN
Temperature Category 50oC / C
electrode thickness 5.5 to 6 micron Al
Dielectric Polypropylene
Dielectric Loss <0.2 watt / Kvar
Capacitor Loss <0.5 watt / Kvar
Impregnate PXE Oil
Discharging Resistor
Cooling Oil & Air Cooled
Protection Internal Fuse
Hazardous & Inflammable Non-Inflammable & Non Hazardous
Connection Delta
Enclosure CRCA sheet
Life Expectancy 1,50,000Hrs
Referring Standard IS 13585 (P1)
Dimension -
www.kotakco.com
www.kotakco.com
   
APP (DL)
Type APP01 to APP025 
Rated Voltage  (UN)  * 415V / 440V / 480V / 525V / 575V 
Frequency 50 HZ
Max. Permissible Overvoltage 1.3 
Max. Permissible Over current 1.9 
Temperature Category 50oC / C 
electrode thickness 5.5 to 6 micron Al 
Dielectric Double Polypropylene 
Dielectric Loss <0.2 watt / Kvar 
Capacitor Loss <0.5 watt / Kvar 
Impregnate PXE Oil 
Discharging Resistor 
Cooling Oil & Air Cooled 
Protection Internal Fuse 
Hazardous & Inflammable Non-Inflammable & Non Hazardous 
Connection Delta 
Enclosure CRCA sheet 
Life Expectancy 2,00,000 Hrs. 
Referring Standard IS 13585 (P1) 
Dimension -
www.kotakco.com
www.kotakco.com
   
Mixed-Di-Electric 
Type MXD01 to 025  
Rated Voltage  (UN)  * 415V / 440V / 480V / 525V / 575V 
Frequency 50 HZ 
Max. Permissible Overvoltage 1.15 x UN 
Max. Permissible Over current 1.7 x IN 
Temperature Category 50oC / C 
electrode thickness 5.5 to 6 micron Al 
Dielectric Polypropylene & Paper 
Dielectric Loss <0.2 watt / Kvar 
Capacitor Loss <1.0 watt / Kvar 
Impregnate PXE Oil 
Discharging Resistor 
Cooling Oil & Air Cooled 
Protection Internal Fuse 
Hazardous & Inflammable Non-Inflammable & Non Hazardous 
Connection Delta 
Enclosure
Life Expectancy 2,00,000 Hrs. 
Referring Standard IS 13585 (P1) 
Dimension -
www.kotakco.com
www.kotakco.com
   
SELF HEALING (MPP)
www.kotakco.com
Simple Pressure Disconnector
Capacitors are manufactured using Zn-Al Metallised Polypropylene Film with reinforcement (Heavy Edge) and slope type film. These special constructions enable capacitor to withstand with high switching surges. Assembly is done in CRCA container / Aluminium Can and is hermetically sealed. Special  3-Ph disconnector is provided for the better safety against bursting
 
SUN (Circular) 
Type SUN 01 to SUN 25
Rated Voltage  (UN)  * 415V / 440V /480V / 525V
Frequency 50 HZ
Max.Permissible Overvoltage 1.3 x UN
Max. Permissible Over current 1.3 x IN
Temperature Category 50oC
Dielectric Polypropylene
Dielectric Loss <0.2 watt / Kvar
Capacitor Loss <0.5 watt / Kvar max.
Impregnate Non PCB, Silicon Oil & Wax /Dry
Electrode Thickness  0.02 to 0.03 micron
Discharging Resistor
Cooling Natural- Air Cooled
Protection Three-Ph Disconnector
Hazardous & Inflammable Non-Inflammable
Connection Delta
Terminals  Pin Type/brass connection with terminal strip
Enclosure Al Container
Life Expectancy 80,000Hrs
Referring Standard IS13340 / IEC 60831
Dimension -
www.kotakco.com
www.kotakco.com
   
SUH(Circular) 
Type SUH 01 to SUH 25
Rated Voltage  (UN)  * 415V / 440V /480V / 525V
Frequency 50 HZ
Max. Permissible Overvoltage 1.4 x UN
Max. Permissible Over current 1.4x IN
Temperature Category 50oC
Dielectric Polypropylene
Dielectric Loss <0.2 watt / Kvar
Capacitor Loss <0.5 watt / Kvar max.
Impregnate Non PCB, Silicon Oil & Wax / Dry
Electrode Thickness  0.02 to 0.03 micron
Discharging Resistor
Cooling Natural- Air Cooled
Protection Three-Ph Disconnector
Hazardous & Inflammable Non-Inflammable
Connection Delta
Terminals  Pin Type/brass connection with terminal strip
Enclosure Al Container
Life Expectancy 1,25,000Hrs
Referring Standard IS13340 / IEC 60831
Dimension -
www.kotakco.com
www.kotakco.com
   
SHN(Rectangle) 
Type SHN 01 to SHN 25
Rated Voltage  (UN)  * 415V / 440V / 480V / 525V
Frequency 50 HZ
Max. Permissible Overvoltage 1.3 x UN
Max. Permissible Over current 1.3 x IN
Temperature Category 50oC
Dielectric Polypropylene
Dielectric Loss <0.2 watt / Kvar
Capacitor Loss <0.5 watt / Kvar max.
Impregnate Non PCB Oil
Electrode Thickness  0.02 to 0.03 micron
Discharging Resistor
Cooling Oil And Air Cooled
Protection Three-Ph Disconnector
Hazardous & Inflammable Non-Inflammable
Connection Delta
Terminals  Threaded Stud
Enclosure CRCA Container
Life Expectancy 1,00,000Hrs
Referring Standard IS13340 / IEC 60831
Dimension -
www.kotakco.com
www.kotakco.com
   
SHH(Rectangle) 
Type SHN 01 to SHN 25
Rated Voltage  (UN)  * 415V / 440V / 480V / 525V
Frequency 50 HZ
Max. Permissible Overvoltage 1.4 x UN
Max. Permissible Over current 1.5 x IN
Temperature Category 50oC
Dielectric Polypropylene
Dielectric Loss <0.2 watt / Kvar
Capacitor Loss <0.5 watt / Kvar max.
Impregnate Non PCB Oil
Electrode Thickness  0.02 to 0.03 micron
Discharging Resistor
Cooling Oil And Air Cooled
Protection Three-Ph Disconnector
Hazardous & Inflammable Non-Inflammable
Connection Delta
Terminals  Threaded Stud
Enclosure CRCA Container
Life Expectancy 1,25,000Hrs
Referring Standard IS13340 / IEC 60831
Dimension
www.kotakco.com
www.kotakco.com
* Non - Standard Voltage rating capacitors will provide on customer request.



HTCAPACITORS
www.kotakco.com
www.kotakco.com
HT Capacitor Technical Data
Rated Output Unit Upto 400Kvar & Bank Upto 40 Mvar
Rated Voltage 3.3 KV TO 33 KV
Frequency 50 / 60 HZ
Connection 3 PH, Delta Or Single / Double Star
Protection Internal / External Fuse
Mounting Vertical / Horizontal
Installation Indoor / Outdoor
Ref. Standard ISS 13925, IEC 871
 
Special Type Of Capacitors
www.kotakco.com
1. Water Cooled Capacitors / Medium Frequency Capacitors
2. Surge Protection Capacitors
3. Energy Storage Capacitors
4. Furnace Duty Capacitors
5. Non Standard Voltage Capacitors
 
Capacitors for Harmonic Filter Applications
www.kotakco.com
Capacitor required for harmonic filter duty will be required to accept given magnitude of various orders of harmonic current which will increase the nominal line current & hence the thermal duty on capacitor. In addition, voltage due to these harmonic currents will appear across the capacitor & will cause an increase in the R.M.S. voltage. Some degree of derating is, therefore, necessary for capacitors used as harmonic filters
The normal current overload permitted in typical power capacitor specification is 1.3 multiplied by nominal current , & in determining this factor due attention has been paid to the fact that a capacitor connected to an ac power system may be required to accept an unknown magnitude of unspecified harmonic currents. In the case of a properly designed harmonic filter the magnitudes & orders of the harmonic currents are known & hence, provided that the permitted over - voltages & KVAR loading are not exceeded , the de-rating factor for the capacitors may not be as great as would be expected.
While Designing these Capacitors due care is taken to avoid imbalance in detuning with reactor over long life operation.
Capacitor of particular harmonic level will be available on customer request.



HARMONICS
What are the Harmonics?
www.kotakco.com
Harmonics are sinusoidal waveform, having frequency in multiples of fundamental (50 Hz) frequency.
 
www.kotakco.com Sources Of Harmonics
Medium Frequency Induction Furnances
Variable Speed Drive
Switch Mode Power Supply
Invertors
Rectifiers
ARC Furnances
CNC m/c'S
Many Other
Demerits And Symptoms Harmonics
Distortion Of Supply Voltage Waveform
Overheating Of Electrical Equipments
Amplification Of Harmonic Current
Errornous Reading Of Power Parameter
Large Current In Neutral Wire - Heating & Fire
Poor P.F. - Increase In Kvah Reading.
Solution
Harmonic Analysis & Solution
Harmonic Filter Unit
Harmonic Filter Panel
 
Harmonic Filter And Harmonic Filter Panel
www.kotakco.com
We offer the 'harmonic filter' solution to above problem impedance path is provided by the series connection of capacitors and reactor has successfully installed these type of harmonic filters in many reputed industries and proved the performance by improving the quality of power.  We also provide the pre and post installation Harmonic analysis study
 
Complete Panel For Centralise Compensation
Available In Contractor Or ThyristorSwitching
Design With Microprocessor Based PF Sensing Relay
Easy To Operate
Fine Load Compensation
 


APFC Panel
www.kotakco.com
Automatic Power Factor Control Panel are use to achieve to unity PF in fluctuating loads. We will suggest you right choice for your POWER FACTOR PROBLEM.
 
Panel consisting of Contactor based of APFC or RTPFC consisting of Thyristor Switching. According to Load condition, we will give you the right solution.
 
Contactor Based APFC Panel
www.kotakco.com
Specifications :
Voltage 415 V / 440 V  or Depends on system voltage
Incomer Protection Isolator / SFU / MCCB / ACB
Outgoing Feeder Incomer Fuse-Base-Fuses / MCB / MCCB/ SFU
Make & Brake Contactor Control : Microprocessor based Intelligent Relay
Capacitor MPP/APP/MXD
Construction 14/16 gauge Compartmentalise/Non-Compartmentalise Panel Special Design for cooling of panel
* Panel dimension will vary according to design.
RTPFC Panel
www.kotakco.com
Specifications
Voltage 415 V / 440 V or depends on system voltage
Incomer Protection Isolator / SFU / MCCB / ACB
Outgoing Feeder Incomer Fuse- Base- Fuses / MCB / MCCB/ SFU
Make & Brake Thyristor
Control Microprocessor based Intelligent Relay
Capacitor MPP/APP/MXD
  * Panel dimension will vary according to design.
 
AMC for APFC Panels
www.kotakco.com
Proper preventive maintenance is important for working of panel. To avoid any problem in working of APFC panel, it needs periodically check up.
 
Following are some parameter will include in our AMC Service
1. Working of panel in both modes.
2. Switchgear Working
3. Capacitor Output
4. Temperature at various points in panel
5. Tightening of components
6. Cleaning
7. Guideline to maintain unity PF
 
www.kotakco.com Harmonic Filter And Harmonic Filter Panel